Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OWNERS KITCHEN EQUIPMENT IS EXISTING FROM A PREVIOUS LOCATION. | |
| 12/12/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*FILL UNUSED OPENINGS IN PANEL. PLEASE VERIFY LISTING LABELS ON ALL EQUIPMENT PLEASE PROVIDE A LETTER FOR DELETED PATIO LIGHTING PLEASE VERIFY DERATING FOR DIMMERS LIGHTS & FANS ROOF: TIGHTEN LOOSE FITTINGS LABEL DISCONNECTS AT PANEL IDENTIFY CONDUCTORS AT TERMINALS PROTECT SEALTITE/NON ?? FLEX FROM SHARP METAL EDGES WHERE IS MAINTANCE RECEPTICAL 210.63 PLAN DO NOT SHOW PANEL ON ROOF |
|
| 12/07/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FOR TEMP CERTIFICATE OF OCCUPANCY |
|
| 10/02/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/26/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. A BOND WILL BE NEEDED FOR TEMP POWER FOR TESTING. 2. W?? ON BONDING WEDGE AND " R" PINS | |
| 09/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BONDING AT SERVICE TO BE AS PER 250.94, 250.102 (A) , 250.66 AS DISCUSSED 2) CIRCUIT CONDUCTOR TO BE COLORED AS PER 210.5 C AMENDMENTS |
|
| 09/20/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |