Permit: T03CM03908

Parcel: 13315305A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/09/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*OWNERS KITCHEN EQUIPMENT IS EXISTING FROM A PREVIOUS LOCATION.
12/12/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*FILL UNUSED OPENINGS IN PANEL.
PLEASE VERIFY LISTING LABELS ON ALL EQUIPMENT
PLEASE PROVIDE A LETTER FOR DELETED PATIO LIGHTING
PLEASE VERIFY DERATING FOR DIMMERS LIGHTS & FANS ROOF:
TIGHTEN LOOSE FITTINGS
LABEL DISCONNECTS AT PANEL
IDENTIFY CONDUCTORS AT TERMINALS
PROTECT SEALTITE/NON ?? FLEX FROM SHARP METAL EDGES
WHERE IS MAINTANCE RECEPTICAL 210.63
PLAN DO NOT SHOW PANEL ON ROOF
12/07/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FOR TEMP CERTIFICATE OF OCCUPANCY
10/02/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/26/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1. A BOND WILL BE NEEDED FOR TEMP POWER FOR TESTING. 2. W?? ON BONDING WEDGE AND " R" PINS
09/22/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BONDING AT SERVICE TO BE AS PER 250.94, 250.102 (A) , 250.66 AS DISCUSSED
2) CIRCUIT CONDUCTOR TO BE COLORED AS PER 210.5 C AMENDMENTS
09/20/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*