Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/09/2006 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 09/20/2005 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* |
| 04/29/2005 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection :* SECURE CONDUITS @ PANEL |
| 04/15/2005 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection :* 1) SEPARATE AND SECURLY SUPPORT M/C CABLES SO AS NOT TO BOND?? CABLES 310-15 (2) ( A0. 2) SUPPORT M/C CABLES AS PER CODE 12' FROM BOXES AND PANEL, AND 6' ON HORIZONTAL AND VERTICAL RUNS 3) PLEASE PREVENT DIE ELECTRIC CONTACT WITH COPPER PIPING. 4) PROTECT CONDUCTOR AT STUDS 300.4 5) SUPPORT CONDUITS WITHIN 3' OF BOXES AND PANEL. 6) BOXES IN STUCCO FOAM WILL NEED APPROVED EXTENDER RINGS OR BROUGHT FLUSH OUT OF COMBUSTIBLES 370-20. 7) WHERE AFTER THE ELECTRICAL PLANS. |