Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM03875
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/30/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
12/26/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) MUST STRAP AND SECURE GAS LINE UNDER PIZZA OVEN. 2) MUST PROVIDE A BACKFLOW PREVENTOR FOR COFFEE MACHINE, TEA DISPENSER AND ICE MAKER. TESTED AND CERTIFIED. 3) TRIPLE COMPT SINK IS DOUBLE TRAPPED AND REQUIRES A FLOW CONTROL VENT TO BE 6" ABOVE FLOOD RIM LEVEL 4) trap arm has offset for triple compt sink. | |
12/09/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |