Permit: T03CM03514

Parcel: 12111001B


Addresses:

5055 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/05/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
11/03/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
10/30/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
10/29/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) TV'S NOT ON PLANS-CHORD AND STRIP OUTLETS NOT ALLOWED FOR PERMANENT WIRING 2) BOND GUTTER ENCLOSURE IN ATTIC AND JUNCTION BOX 3) FILL UNUSED OPENINGS IN JUNCTION BOX 4) PROPERLY GROUND FLOURESCENT LIGHT FIXTURES 5) DATA NOT TO BE SUPPORTED FROM CONDUIT
10/17/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) WE HAVE EXPOSED CONDUCTORS-PLEASE COVER OR REMOVE 2) SUPPORT M/C CABLE 3) FILL UNUSED OPENINGS 4) CONDUIT TO DOOR OPENERS TO BE SUPPORTED TO STRUCTURE 5) WE HAVE EXCESSIVE PAINT ON DEVICE TERMINALS 110.12 6) IF BOX IS MORE THAN 1/4" FROM SURFACE AN APPROVED EXTENDER RING IS NEEDED-METAL NOT APPORVED 370.20 7) ELECTRIC BOXES TO BE ACCESSIBLE 8) MAINTAIN WORKING CLEARANCE IN FRONT OF PANELS AT ALL TIMES 9) BOXES ARE NEEDED FOR CEILING LIGHTS 10) CONTACT STEVE LONG FOR TEMP C OF O
09/09/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) REFRESHMENTS BAR. 2) BATHROOMS OK.