Permit: T03CM02901

Parcel: 11301095C

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
09/30/2004 ELECTRIC - UFER Approved IVRS - Inspection :*APPROVED. 1/0 COPPER UFER TO REBAR.
09/29/2004 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*/ 1) PLANS CALL FOR 1/0 FOR UFER-WE HAVE ONLY #4