Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 02/17/2004 |
ELECTRIC - UNDERGROUND |
|
Approved |
IVRS - Inspection 0000* |
| 02/13/2004 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) U.G. SECONDARYS MUST BE 24" BELOW FINISH GRADE OVER DRIVEWAYS, ETC. SEE 300-5 NEC. 2) INSTALL BOND BUSHINGS IN SVS EQUIPMENT, 250 - 94 UPC. |