Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/31/2003 |
SHEET ROCK NAILING |
|
Approved |
IVRS - Inspection 0000* |
| 12/24/2003 |
SHEET ROCK NAILING |
|
Partial Approval |
IVRS - Inspection 0000* NEED METAL BOXES FOR COMM LINES IN FIRE WALL. |
| 12/23/2003 |
SHEET ROCK NAILING |
|
Denied |
IVRS - Inspection 0999* 1) SEE KEY NOTE 3 pp A-1. 2) PROVIDE ACCESS FOR INSP OF FIRE BARRIERS ABOVE CEILING. 3) YOU MAY NOT USE PLASTER RINGS FOR DATA CALBES IN A FIRE BARRIER. REPLACE WITH 1 HR RATED OUTLET BOXES. |