Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2003 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*/ 1) INSPECTED CONDENSATE DRAIN LINES, ALL DUCT ABOVE T-BAR. CHECKED DUCT SMOKE DETECTORS. WILL CHECK OPERATION OF DETECTORS ON FINAL. OK FOR CEILING TILES |
| 11/06/2003 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) PROVIDE MINIMUM 1/8" PER FT. SLOPE ON CONDENSATE DRAIN LINES 2) CONNECT ELECTRIC TO DUCT SMOKE DETECTORS. EVERYTHING ELSE IS OK. RECALL FOR INSPECTION |
| 10/02/2003 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/SUSPENDED HARD DUCT IN ATTIC. |