Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2005 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* | |
| 05/13/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Nothing done from all previous inspections Comply with all requests |
|
| 05/04/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MUST COMPLY WITH THE LAST 2 INSPECTIONS 2) PROVIDE PROOF OF 1ST LIFT INSPECTION 3) NEXT FAILURE WILL RESULT IN A REINSPECTION FEE |
|
| 02/03/2005 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS/PERMIT ON SITE 2) NO REINFORCING STEEL IN FIRST CELL EITHER SIDE OF WINDOWS AND DOORS 3) INSPECTION, ITEMS FROM 12/23/04 NOT COMPLIED WITH |
|
| 12/23/2004 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PLANS/PERMIT ON SITE 2) PART OF SECOND LIFT WAS GROUTED WITHOUT INSPECTION NOW THERE IS NO OVERLAP ON VERTICAL REBAR. TAKE WALL DOWN TO EXPOSE 20" OF OVERLAP OF FIRST LIFT REBAR 3) BOND BEAM BLOCK PUT IN UPSIDE DOWN. YOU MUST HAVE 1 1/2" OF CONCRETE ABOVE BOND BEAM REBAR 4) CANNOT SEE HORIZONTAL DURA WALL WIRE IN WALL. PROVIDE PROOF OF INSTALLATION |
|
| 08/06/2004 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :*/ 1) NOTE: FIRST LIFT OK TO GROUT |