Permit: T03CM02265

Parcel: 138020560


Addresses:

701 W CALLE MILU

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
06/28/2005 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
05/13/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Nothing done from all previous inspections
Comply with all requests
05/04/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MUST COMPLY WITH THE LAST 2 INSPECTIONS
2) PROVIDE PROOF OF 1ST LIFT INSPECTION
3) NEXT FAILURE WILL RESULT IN A REINSPECTION FEE
02/03/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS/PERMIT ON SITE
2) NO REINFORCING STEEL IN FIRST CELL EITHER SIDE OF WINDOWS AND DOORS
3) INSPECTION, ITEMS FROM 12/23/04 NOT COMPLIED WITH
12/23/2004 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS/PERMIT ON SITE
2) PART OF SECOND LIFT WAS GROUTED WITHOUT INSPECTION NOW THERE IS NO OVERLAP ON VERTICAL REBAR. TAKE WALL DOWN TO EXPOSE 20" OF OVERLAP OF FIRST LIFT REBAR
3) BOND BEAM BLOCK PUT IN UPSIDE DOWN. YOU MUST HAVE 1 1/2" OF CONCRETE ABOVE BOND BEAM REBAR
4) CANNOT SEE HORIZONTAL DURA WALL WIRE IN WALL. PROVIDE PROOF OF INSTALLATION
08/06/2004 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*/ 1) NOTE: FIRST LIFT OK TO GROUT