Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/13/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/09/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999* DENIED. 1) TRUSS BRACE RUT RUN NOT IN FIREST WEB EAST OF RIDGE 2) 3PT BEARING NOT COMPLETE AT EAST BAY WINDOW. 3) FIREPLACE CHIMNEY NOT IN. OK TO INSULATE & DRY WALL ALL BUT REAPAIR AREAS |
| 01/08/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) 3 PT BEARING TRUSSES S02' MUST BEAR ON EAST WALL AND WEST 2) TRUSS BRACE NOT INSTALLED SEE TRUSS DRAWING 3) BLOCK ALL MECHANICAL BOOTS 3 SIDES 4) FIRE PALCE HEARTH NOT PER PLAN 5) FIRE STOP 2 LAYERS 1/2" OSB 6) FIREPLACE FLUE NOT IN |
| 01/06/2004 |
FRAMING |
|
Cancelled |
IVRS - Ri canceled |
| 12/23/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ no city approved engineering truss drawings on site. overbuild rafters require u-26 hangers at ridge board and collars at 4'. fire block all furred out ares. |