Permit: T03CM01967

Parcel: 11615077C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/24/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
06/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) NO COMPLIANCE WITH LAST INSPECTION WRITE-UP A RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NOT COMPLIED
06/19/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245* PARTIAL CORRECTIONS LIST 1. " J'' BOXES IN ATTIC ARE WITHOUT COVERS & WIRING MAY BE UNSPLICED. 2. THE EXISTING PANEL A MUST BE FITTED WITH A 200AMP MAIN CKT-BRKR. PER PANEL SCHEDULE. 3. INSTALL 30AMP DISCONNECT W/FUSES (PER PLAN) ON WATER HEATER FEEDER CIRCUITS 39 & 41 4. WALK-IN BOXES THE LIGHTS DON'T TURN ON. 5. INSTALL DISCONNECTS & FUSES FOR WALK IN BOXES AS SPECIFIED ON PLAN SHET E1. 6. SET UP LADDER TO ACCESS ROOF ON NEXT INSPECTION.