Permit: T03CM01962

Parcel: 118051440


Addresses:

1717 S VIA ARRIBA

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/04/2003 FRAMING Approved IVRS - Inspection 0000*
08/01/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) INSTALL CLEANOUTS AT BATHS 2) INSTALL RED HEADS AT PORCH 3) NAIL THA HANGER 4) COMPLETE LATH 5) INSTALL H2.5'S AT PORCH 6) DO NOT BUNDLE WIRING AT HOME RUN 7) NAIL PLATE ELECTRICAL AT MASTER BEDROOM 8) SHIM HEADERS 9) CHECK U-VALUES AT FINAL FRAME
07/31/2003 FRAMING Denied IVRS - Inspection 0160*/ 1) SEE PREVIOUS INSPECTION 2) ALL WINDOWS NOT INSTALLED 3) NAIL PLATES 4) TEST WASTE LINES
07/17/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) H2.5 CLIPS AT TRUSSES MISSING NAILS THROUGHOUT HOUSE 2) OVERSPAN FRAMING AT GARAGE 3) NAIL PROTECT PLUMBING WITHIN 1 1/2" FROM EDGE OF STUD 4) NAIL PROTECT ALL ELECTRICAL WITHIN 1 1/4" FROM EDGE OF STUD 5) PLUMBERS TAPE NOT ALLOWED FOR SUPPORTING VENTS 6) SECURE ALL WATER LINES 7) PLYWOOD AT PLATFORM NOT INSTALLED PER CODE 8) ELECTRIC NOT COMPLETE AT ATTIC AREA 9) THJA26 HANGER MISSING NAILS 10) STOPPED INSPECTION-RECALL WHEN READY-TO MANY ITEMS 11) GIRDER TRUSS REQUIRES DOUBLE STUDS 12) DWV'S AND WATER LINES PASSED TEST