Permit: T03CM01900

Parcel: 140290570


Addresses:

3131 E TRANSCON WY

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
08/29/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*/1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAINS TO EXISTING BLDG DRAINS OK. 3) OK TO BACKFILL TRENCH. 4) NOTE: PLEASE PROVIDE COMPACTION RESULTS OF TRENCH BACKFILL AT TIME OF FINAL INSPECTION.
08/25/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/1) 12" CORRUGATED PVC FROM BLDG TO BEYOND BLDG LINE - AS HIGHLIGHTED ON C-4, OK TO COVER, PENDING VERIFICATION OF APPROVAL OF MATERIAL TYPE.
08/21/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/1) EXTENSION OF 12" RAIN LEADER UNDER STRUCTURE REQUIRES A WATER TEST FROM ROOF TO BEFORE CONNECTION TO GALVENIZED STORM DRAIN. 2) PLEASE PROVIDE LISTING ON CORRGATED PYC UNDER STRUCTURE.
08/15/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK. 2) THIS INSPECTION IS FOR ROUGH PLUMBING, FOR RESTROOMS BETWEEN GRID #4 EAST TO #8 AND BETWEEN GRID LINE 8 NORTH TO 10 ONLY. 3) 8" RWC IS OK AS NOTED ON PLAN. 4) NOTE: EXISTING BLDG SEWER IS SDR-35. THIS MATERIAL IS NOT APPROVED WITHIN THE STRUCTURE.