Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/29/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*/1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAINS TO EXISTING BLDG DRAINS OK. 3) OK TO BACKFILL TRENCH. 4) NOTE: PLEASE PROVIDE COMPACTION RESULTS OF TRENCH BACKFILL AT TIME OF FINAL INSPECTION. |
| 08/25/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/1) 12" CORRUGATED PVC FROM BLDG TO BEYOND BLDG LINE - AS HIGHLIGHTED ON C-4, OK TO COVER, PENDING VERIFICATION OF APPROVAL OF MATERIAL TYPE. |
| 08/21/2003 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1) EXTENSION OF 12" RAIN LEADER UNDER STRUCTURE REQUIRES A WATER TEST FROM ROOF TO BEFORE CONNECTION TO GALVENIZED STORM DRAIN. 2) PLEASE PROVIDE LISTING ON CORRGATED PYC UNDER STRUCTURE. |
| 08/15/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK. 2) THIS INSPECTION IS FOR ROUGH PLUMBING, FOR RESTROOMS BETWEEN GRID #4 EAST TO #8 AND BETWEEN GRID LINE 8 NORTH TO 10 ONLY. 3) 8" RWC IS OK AS NOTED ON PLAN. 4) NOTE: EXISTING BLDG SEWER IS SDR-35. THIS MATERIAL IS NOT APPROVED WITHIN THE STRUCTURE. |