Permit: T03CM01900

Parcel: 140290570


Addresses:

3131 E TRANSCON WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/04/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/02/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ LABEL MAIN SWITCH FOR NEW PANEL - 1 + 1 AT SERVICE SECTION.
05/25/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT J-BOXES ABOVE PARTITIONS IN SERVICE DEPT. OFFICES, TERMINATE EXPOSED WIRES, COVER BOXES. 2) LABEL DISCONNECTS AND STARTERS TO I.D. EQUIPMENT.
02/13/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) COMPLETE MAKE IN J-BOXES ABOVE CEILING. 2) SUPPORT CONDUIT WITHIN 3' EACH TERMINATION AND AT 10' INTERVALS. 3) COMPLETE TERMINATIONS IN PANELS, BONDING AT X-FORMER, PANEL SCHEDULES. 4) ALSO NOTE: THAT UFER NOT APPROVED, LABEL EQUIPMENT AS NECESSARY. 5) INSTALL DISCONNECT SWITCHES AND LABEL FOR A/C UNITS.
12/31/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) TEMP C OF O 2) OK FOR STORING PRODUCT IN NORTH WEST SECTION AREA TO BE FENCED OFF