Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ LABEL MAIN SWITCH FOR NEW PANEL - 1 + 1 AT SERVICE SECTION. |
|
| 05/25/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT J-BOXES ABOVE PARTITIONS IN SERVICE DEPT. OFFICES, TERMINATE EXPOSED WIRES, COVER BOXES. 2) LABEL DISCONNECTS AND STARTERS TO I.D. EQUIPMENT. |
|
| 02/13/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) COMPLETE MAKE IN J-BOXES ABOVE CEILING. 2) SUPPORT CONDUIT WITHIN 3' EACH TERMINATION AND AT 10' INTERVALS. 3) COMPLETE TERMINATIONS IN PANELS, BONDING AT X-FORMER, PANEL SCHEDULES. 4) ALSO NOTE: THAT UFER NOT APPROVED, LABEL EQUIPMENT AS NECESSARY. 5) INSTALL DISCONNECT SWITCHES AND LABEL FOR A/C UNITS. | |
| 12/31/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) TEMP C OF O 2) OK FOR STORING PRODUCT IN NORTH WEST SECTION AREA TO BE FENCED OFF |