Permit: T03CM01865

Parcel: 12213143C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/14/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/12/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOXES MORE THAN 1/4" AT NON-COMBUSTIBLES AND FLUSH AT COMBUSTIBLES TO USE AN APPROVED EXTENDER RING 316.20 (STUCCO)
2. TERMINATE GROUNDING EQUIPMENT CONDUCTOR AT LIGHT FIXTURES.
3. TIGHTEN LOOSE NON-METALLIC FLEX FITTINGS
4. WHERE ARE PLAN REVISIONS REQUESTED ON 5/5/05?
12/09/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTHING WAS DONE ON ROOF DISCONNECTS EXCEPT LOOSEN FITTINGS, INSTALL REDUCING WASHER AND TIGHTEN FITTING
12/07/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL AC DISCONNECTS TO HAVE WHITE WIRE TAPED BLK
2. AC DISCONNECT #7 ON ROOF RUN FLEX & CONNECT STRAIGHT INTO BOX - NOW ITS TWISTING KO
3. OUTSIDE WALL LIGHTS NOT INSTALLED - GET OK TO OMIT AND WILL NEED WEATHERPROOF COVERS.
4. UNITS TO BE ENERGIZED SO TEST ON GFI'S, ARC FAULTS, SMOKE DETECTORS CAN BE MADE - NO ONE HERE - I DON'T KNOW IF OK TO ENERGIZE - WILL NOT ENERGIZE ON MY OWN #5 NOT ON
5. INSIDE UNIT 6 & 7 OK
12/02/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*OK TEMP POWER FOR TEST UNITS 5,6,7 CLEARED PER BOB SUBA