Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOXES MORE THAN 1/4" AT NON-COMBUSTIBLES AND FLUSH AT COMBUSTIBLES TO USE AN APPROVED EXTENDER RING 316.20 (STUCCO) 2. TERMINATE GROUNDING EQUIPMENT CONDUCTOR AT LIGHT FIXTURES. 3. TIGHTEN LOOSE NON-METALLIC FLEX FITTINGS 4. WHERE ARE PLAN REVISIONS REQUESTED ON 5/5/05? |
|
| 12/09/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTHING WAS DONE ON ROOF DISCONNECTS EXCEPT LOOSEN FITTINGS, INSTALL REDUCING WASHER AND TIGHTEN FITTING |
|
| 12/07/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL AC DISCONNECTS TO HAVE WHITE WIRE TAPED BLK 2. AC DISCONNECT #7 ON ROOF RUN FLEX & CONNECT STRAIGHT INTO BOX - NOW ITS TWISTING KO 3. OUTSIDE WALL LIGHTS NOT INSTALLED - GET OK TO OMIT AND WILL NEED WEATHERPROOF COVERS. 4. UNITS TO BE ENERGIZED SO TEST ON GFI'S, ARC FAULTS, SMOKE DETECTORS CAN BE MADE - NO ONE HERE - I DON'T KNOW IF OK TO ENERGIZE - WILL NOT ENERGIZE ON MY OWN #5 NOT ON 5. INSIDE UNIT 6 & 7 OK |
|
| 12/02/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK TEMP POWER FOR TEST UNITS 5,6,7 CLEARED PER BOB SUBA |