Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/31/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/02/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NEED VERIFICATION ALL POST TO BEAM, POST TO CONCRETE CONNECTIONS; ALL BOTTOM PLATES TO CONCRETE, BEARING STUDS TO PLATES TOP AND BOTTOM; TOP PLATES TO BEAMS, BEAMS TO RAFTERS 2) FILL ALL NAIL HOLES IN A35'S ETC.. 3) STRAP ALL PLUMBING WITHIN 1 1/2" OF STUD; RAFTER FACE 4) STRAP ? ELECTRIC WITHIN 1 1/4" OF STUD-RAFTER FACE 5) WATER TEST DWV PIPING THROUGH ROOF 6) MUST COMPLETE ALL ELECTRIC, PLB, MECH GAS AS WELL AS FRAMING THEN RECALL FOR INSPECTION 7) PLAN CALLS FOR 2-2 X 10 EACH SIDE SKI LIGHTS 8) HEADERS NOT PER PLAN 9) HEADERS OVER WINDOWS INCORRECTLY INSTALLED 10) STRAP ALL HEADERS TO BEARING BELOW 11) WILL NEED TO REMOVE SHEETROCK, PLYWOOD, ETC.. TO INSPECT FRAMING 12) STOPPED INSPECTION |
|
| 03/15/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
| 01/21/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
| 09/17/2003 | FRAMING | Denied | IVRS - Inspection 0999* |