Permit: T03CM01126

Parcel: 123030660


Addresses:

2901 E ADAMS ST

Inspection Status: Denied

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/15/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SOUTH AND NORTH EXT. OUTLET NOT GFI AND NEEDS BUBBLE COVERS
2) A/C DISCONNECTS ARE OVER FUSED
3) CUT CLEANOUTS ON N.E. PORCH TO BE FLUSH WITH SLAB
4) CUT POSTS OFF CONCRETE AT S.E. PORCH
5) GROUNDS AND NEUTRALS MUST BE SAME GAUGE UNDER SCREW (2 MAX)
6) TRAP CONDENSATES AND DISCONNECT H20 HEATER PAN FROM CONDENSATE DRAIN
7) NEED SECONDARY CONDENSATE DRAINS
8) ROOF OUTLETS NOT GFI PROTECTED
9) SMOKIES INOPERABLE
10) NEED HANDRAILS TO RETURN TO WALL
11) CLAMP OPEN FIREPLACE DAMPER
12) RAISE DISHWASHER DRAIN LINE TO COUNTER BOTTOM
13) PROTECT EXPOSED WIRING IN SHOP AND GFI PROTECT
07/26/2004 BUILDING - FINAL Denied IVRS - Inspection :HANDRAK MUST TERMINATE INTO WALL OR AT SAFTEY TERMINAL
KITCHEN ISLAND MUST HAVE GFI OUTLET
SHEET METAL SCREWS NO PERMITTED IN ELEC PANEL DEAD FRONT
A/C DISCONNECTS BEHIND UNITS NOT PERMITTED
HOSE BIBBS REQUIRE ANTI-SYPHON DEVICE