Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2004 |
MECHANICAL - ABOVE CEILING |
|
Approved |
|
| 01/12/2004 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ SEAL ALL JOINTS ON METAL DUCT. STRAP FLEX DUCT IF OVER 5' IN LENGTH. SUPPORT CONDENSATE DRAIN FROM FAN COILS. INSULATE BARE METAL DUCT AS NEEDED. RECALL FOR INSP. |
| 12/24/2003 |
MECHANICAL - ABOVE CEILING |
|
Denied |
|
| 12/18/2003 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ NEED TO SEE DUCT SMOKE DETECTORS WIRED AND POWERED UP. |
| 12/08/2003 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ NEED TO SEE DUCT SMOKE DETECTORS IN MAIN SALES FLOOR. |
| 12/04/2003 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ INSPECTION ON MAIN SALES FLOOR AREA. PROVIDE DUCT SMOKE DETECTORS. CONNECT RETURN DUCT AND CONNECT SUPPLY DUCT TO DIFFUSER ALL UNITS. LEAVE OUT CEILING TILES IN THESE AREAS. |
| 11/28/2003 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |