Permit: T03CM00901

Parcel: 133552310

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/21/2004 MECHANICAL - INTERMEDIATE Approved
12/24/2003 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*
11/13/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ inspected condensate drain lines and suspended rough duct, - ok to proceed. still need to see final drain connectors at front of store. need to see fire dampers and openings prior to installing angle iron.
11/03/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ CONDENSATE DRAIN LINES REQUIRE MIN. 1/8" PER FT SLOPE. RECALL FOR INSPECTION.