Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/26/2004 |
ELECTRIC - ABOVE CEILING |
|
Approved |
|
| 01/09/2004 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |
| 12/31/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ OK POWER POLES AND RELOC. SYSTEM AT ELECTRONICS, SPORTING GOODS, TOYS, GAMES, KITCHE, SMALL ELECTRICS, FURNITURE, HOME OFFICE, PARTIAL CUSTOMER SERVICE AREA. INSTALL SUPPORT AT J BOXES FOR RELOC WITHIN 12". |
| 12/24/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ OFFICE AREAS OK. 1 - 2X4 MISSING, 1 IN HALLWAY. NO SEISMIC TIES. DELI/DINING AREA NOT READY. |
| 12/18/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ ABOVE CEILING @ GUEST SERVICE - PARTIAL, ROOM 129 - APPROVED. FIRE PUMP: OK TO CLEAR TESTING - SUBJECT TO OTHER INSP. |
| 12/09/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MAIN SALES FLOOR ABOVE COMPLETE XCENT POWER POLES 2) LP-10 TO LP-10A 2" REROUTED APPROVAL |
| 12/05/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ NORTH 1/3 OF SALES FLOOR APPROVED, EXCEPT POWER POLES. ROOFTOP APP. EXCEPT A/C - 1,2 & 3. |
| 11/28/2003 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) ATTACH SUPPORT WIRES BOTH ENDS 300.11 2) SUPPORT RELOCATE CABLES AS PER 604 AND 334.10 6' + 12" 3) PLEASE FINISH ATTACHING FIXTURES TO GRID 410.16 |
| 11/26/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ APPROVE TEMP POWER TO ENERGIZE M.D.S. AND BLANK OFF F.P. METER. OK MDP1 OR MDP2. NEED PROPER CLEARANCE IN FRONT OF SERVICE. DISCONNECT 'FIRE PUMP'. PLEASE REVERSE DOOR OPENING [ TO GO OUTBOARD ] AT COMPRESSOR CONTROL PANEL ROOM. |
| 11/13/2003 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*/ NOTES: 1) EDC ROOM IS UL LISTED AND PRE-FABBED WITH POWER AND LIGHTING EQUIP, PANELS, X-FORMER, CONTRACTORS. 2) ALSO LIGHTING RE-LOC SYSTEMS HAS FULL SIZE GROUND AND IS UL LISTED. |