Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/01/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ SHELL ONLY - NO T.I.'S INCLUDED. |
| 09/30/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ DUCT SMOKE DETECTORS ON END UNITS NOT WIRED. |
| 09/29/2003 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 09/25/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ STILL NEED TO SEE LETTER FROM ENGINEER ON DUCT SMOKE DETECTORS. |
| 09/23/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. 2) PERMANENTLY LABEL EQUIPMENT WITH SUITE NUMBER. 3) SUITE NUMBER 170, INSTALL DUCT SMOKE DETECTOR. PROVIDE A LETTER FROM ENGINEER IF DELETING DUCT SMOKE DETECTORS. RECALL FOR FINAL. |