Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM00269
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ SHELL ONLY - NO T.I.'S INCLUDED. | |
| 09/30/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ DUCT SMOKE DETECTORS ON END UNITS NOT WIRED. | |
| 09/29/2003 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
| 09/25/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ STILL NEED TO SEE LETTER FROM ENGINEER ON DUCT SMOKE DETECTORS. | |
| 09/23/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. 2) PERMANENTLY LABEL EQUIPMENT WITH SUITE NUMBER. 3) SUITE NUMBER 170, INSTALL DUCT SMOKE DETECTOR. PROVIDE A LETTER FROM ENGINEER IF DELETING DUCT SMOKE DETECTORS. RECALL FOR FINAL. |