Permit: T03CM00269

Parcel: 141148180


Addresses:

9136 E VALENCIA RD


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T03CM00269

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2003 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection 0000*
07/18/2003 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection 0000*/ 1) LIGHT POLE BASES NOT PER PLAN YOU NEED MINIMUM 6'-6" BELOW GRADE. YOUR CONCRETE POLE FORM SHOULD NOT EXTEND MORE THAN 6" BELOW GRADE 2) FOOTING FOR TRASH ENCLOSURE WAS APPROVED BY ME ON 7/11/03
07/14/2003 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection 0999*/ 1) TRASH ENCLOSURE FOOTING POURED WITHOUT INSPECTION APPROVAL
06/18/2003 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection 0000*/ 1) MAIN BLDG COMPLETE, SCREEN WALL FOOTINGS FOR TRASH ENCLOSURE TO BE AT LATER DATE
06/17/2003 EXCAVATION/LAYOUT REBAR & ZON Denied 1) PER DETAIL NOTE 7/52 PLEASE INSTALL END OF WALL AND JAMB BARS ONE VENT PER CELL LAST 2 CELLS. CORNERS AND INTERSECTION PER DETAIL 15/54 2 VERTS AT INTERSECTION AND ONE IN EACH ADJACENT CELL 2) PLEASE PLACE AB'S 3) OK TO POUR CONT. FOOTING LINES 1, 5 AND C WHEN SPECIAL INSPECTOR CONFIRMS CORRECTION