Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 07/28/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Approved |
IVRS - Inspection 0000* |
| 07/18/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) LIGHT POLE BASES NOT PER PLAN YOU NEED MINIMUM 6'-6" BELOW GRADE. YOUR CONCRETE POLE FORM SHOULD NOT EXTEND MORE THAN 6" BELOW GRADE 2) FOOTING FOR TRASH ENCLOSURE WAS APPROVED BY ME ON 7/11/03 |
| 07/14/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
IVRS - Inspection 0999*/ 1) TRASH ENCLOSURE FOOTING POURED WITHOUT INSPECTION APPROVAL |
| 06/18/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MAIN BLDG COMPLETE, SCREEN WALL FOOTINGS FOR TRASH ENCLOSURE TO BE AT LATER DATE |
| 06/17/2003 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
1) PER DETAIL NOTE 7/52 PLEASE INSTALL END OF WALL AND JAMB BARS ONE VENT PER CELL LAST 2 CELLS. CORNERS AND INTERSECTION PER DETAIL 15/54 2 VERTS AT INTERSECTION AND ONE IN EACH ADJACENT CELL 2) PLEASE PLACE AB'S 3) OK TO POUR CONT. FOOTING LINES 1, 5 AND C WHEN SPECIAL INSPECTOR CONFIRMS CORRECTION |