Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM00220
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
07/30/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*/ NOTES: 1) COMPLETE CONDUIT INSTALL AND SUPPORT IN KITCHEN WALLS 2) FLEX CONDUIT SUPPORTED WITH CEILING WIRES. MUST HAVE WIRES TIED OFF AT BOTH ENDS. 300.11A NEC 3) CONNECT FIXTURE CORDS PER MANUFACTURER LISTING | |
05/02/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* |