Permit: T03CM00191

Parcel: 107140530


Addresses:

2546 N FONTANA AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
01/06/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*
11/26/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) MAKE UP ALL GROUNDS IN ELECTRIC BOXES AND SECURE WITH MECHANICAL FASTENERS 2) NAIL PROTECT ALL PLUMBING WITHIN 1 1/4" OF STUD WALL SURFACES INCLUDING GAS LINES 3) KITCHEN SINK VENT NOT COMPLETE 4) GROUND UNIONS NOT ALLOWED INCLOSED IN WALL FOR GAS LINE USE A LEFT AND RIGHT HANDED NIPPLE AND COUPLING 5) HARD WIRED SMOKE DETECTORS REQUIRED IN BEDROOM AND ROOM LEADING TO BEDROOM 6) INSTALL 1 1/2" (R.6) INSUALTION AND VAPOR BARRIER ON DUCT WORK 7) GALVANIZED PIPE AND VALVE NOT ALLOWED IN SLAB/WALL 8) CLOSET LIGHT MUST BE AT LEAST 12" IN FRONT OF SHELF 9) ALL WIRES MUST TERMINATE IN APPROVED BOXES