Permit: T03BU01241

Parcel: 137117590

Inspection Status: Approved

Inspection History: BUILDING PRE-SLAB

Date Description Inspector Results Comments
05/21/2003 BUILDING PRE-SLAB Approved IVRS - Inspection 0000*NAIL NOT ALLOWED THRU ELECTRIC BOXES TO SUPPORT BOXES. REMOVE NAILS AND SUPPORT WITH SCREWS ON ONE SIDE OR CHANGE BOXES TO REPAIR BOXES.
2.) METAL ELECTRIC BOXES REQUIRE PLASTIC BUSHING IN ALL KNOCK OUTS.
3.) ALL METAL ELECTRIC BOXES MUST BE GROUNDED.
4.) UNTREATED WOOD CANNOT BE IN CONTACT WITH CONCRETE OR LOCATION WITHIN 6" OF SOIL.
5.) OPEN A SECTION OF NORTH AND EAST WALL ALLPY BOTTOM FOR A LENGTH OF 24" AND 12" HIGH.
6.) WINDOW IS TOO SMALL FOR EMERGENCY EXIT. OPENING MUST BE A MINMUM OF 20" WIDE AND 24" HIGH WITH MINIMUM SIZE OF OPENING 5.7 SQ FT MAXIMUM SILL HEIGHT 44"
7.) NOW OPENING BARS ARE NOT ALLOWED ON BED ROOM WINDOWS.
8.) HARD WIRED SMOKE DETECTOR REQUIRED IN NEW BEDROOM.