Inspection History Details
Inspection Status: Violation
Inspection History: INITIAL CODE VIOLATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2002 | INITIAL CODE VIOLATION | Violation | THE FIRE WAS CONFINED TO THE ROOF SURFACE AND THE ROOF MOUNTED EVAPORATION COOLER. NO STRUCTURAL DAMAGE TO THE HOUSE. THE HOUSE IS USED AS AN R2 GROUP HOME. I ADVISED THE OWNER TO CONTACT AND ELECTRICAL CONTRACTOR TO REPLACE THE ELECTRICAL RECEPTACLES AND CORDS ON THE DAMAGED EVAP. COOLER. ELECTRIC CORD ON ROOF. ROOF TOP EVAPORATIVE COOLER. NO DAMAGE. ELECTRICAL CORDS CONNECTING EVAP. COOLER TO RECEPTACLES WERE DAMAGED. PLUMBING NONE. MECHANCIAL: THE EVAP. COOLER ON ROOF RECEIVED MINOR DAMAGE. SUMMARY: CORDS EXTENDING FROM EVAP. COOLER TO CONNECTING ELECTRICAL BOX ON ROOF BURNED AND MELTED DUE TO HIGH RESISTANCE CONNECTION. FU. 11/14/02 |