Case Details

Status:

CLOSED

Type:

COM: FIRE
Address:

Entered Date:

10/15/2002

Applicant:

CHIN GEORGE H & NELSY JT/RS

Description:

EMERGENCY: ELECTRICAL FIRE.

Outstanding Inspections

Case Number: T02VL02102
Case Status: CLOSED
Case Description: COM: FIRE
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
10/14/2002 INITIAL CODE VIOLATION MCAPISTR Violation THE FIRE WAS CONFINED TO THE ROOF SURFACE AND THE ROOF MOUNTED EVAPORATION COOLER. NO STRUCTURAL DAMAGE TO THE HOUSE. THE HOUSE IS USED AS AN R2 GROUP HOME. I ADVISED THE OWNER TO CONTACT AND ELECTRICAL CONTRACTOR TO REPLACE THE ELECTRICAL RECEPTACLES AND CORDS ON THE DAMAGED EVAP. COOLER. ELECTRIC CORD ON ROOF. ROOF TOP EVAPORATIVE COOLER. NO DAMAGE. ELECTRICAL CORDS CONNECTING EVAP. COOLER TO RECEPTACLES WERE DAMAGED. PLUMBING NONE. MECHANCIAL: THE EVAP. COOLER ON ROOF RECEIVED MINOR DAMAGE. SUMMARY: CORDS EXTENDING FROM EVAP. COOLER TO CONNECTING ELECTRICAL BOX ON ROOF BURNED AND MELTED DUE TO HIGH RESISTANCE CONNECTION. FU. 11/14/02

Completed Inspections

Case Status: CLOSED
Case Number: T02VL02102
Case Description: COM: FIRE
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/14/2002 FOLLOW UP CODE VIOLATION MCAPISTR Approved OK TO CLOSE PROBLEM HAS BEEN CORRECTED.