Inspection Status: Partial Approval
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2002 |
PLUMBING - FINAL |
|
Partial Approval |
1.) SOIL WATER TEST IS OK 2.) HCS CONNECTION @ P.L. IS OK 3.) P.O.C. OF EXSISTING BLDG. DRAIN TO NEW BLDG. SEWER IS OK 4.) NOTE: BACKWATER VALVE WILL REQUIRE A PIT. SEE SECTION 710.6 94 UPC. 5.) OK TO BACKFILL TRENCH. |
| 07/29/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST PROVIDE WATER TEST ON SYSTEM SEE SECTION 723.0 94 UPC. 2.) PLEASE PROVIDE PLOT PLAN TO VERIFY LOCATION OF PROPERTY LINE TO BE CERTAIN THAT BLDG. SEWER IS ON SAME LOT AS BLDG. SEE SECTION 721.1 94 UPC. 3.) TWO WAY C.O. MUST BE LOCATED WHERE BLDG. DRAIN CONNECTS TO BLDG. SEWER SE 719.1 94 UPC. 4.) NOTE: TWO WAY C.O. HAS DEAD SPACE BETWEEN COMBOS. ONE OF THESE FITTING MUST BE REVERSED 5.) DO NOT COVER TRENCH. |