Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02PL01360

Parcel: 113102860


Addresses:

1833 E WATER ST #01

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/01/2002 PLUMBING - FINAL Partial Approval 1.) SOIL WATER TEST IS OK 2.) HCS CONNECTION @ P.L. IS OK 3.) P.O.C. OF EXSISTING BLDG. DRAIN TO NEW BLDG. SEWER IS OK 4.) NOTE: BACKWATER VALVE WILL REQUIRE A PIT. SEE SECTION 710.6 94 UPC. 5.) OK TO BACKFILL TRENCH.
07/29/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST PROVIDE WATER TEST ON SYSTEM SEE SECTION 723.0 94 UPC. 2.) PLEASE PROVIDE PLOT PLAN TO VERIFY LOCATION OF PROPERTY LINE TO BE CERTAIN THAT BLDG. SEWER IS ON SAME LOT AS BLDG. SEE SECTION 721.1 94 UPC. 3.) TWO WAY C.O. MUST BE LOCATED WHERE BLDG. DRAIN CONNECTS TO BLDG. SEWER SE 719.1 94 UPC. 4.) NOTE: TWO WAY C.O. HAS DEAD SPACE BETWEEN COMBOS. ONE OF THESE FITTING MUST BE REVERSED 5.) DO NOT COVER TRENCH.