Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) NEW PIPING UNDERGROUND COVERED BEFORE INSPECTION. 2.) WHERE PIPING MEETS, A RIGHT LEFT NIPPLE AND COUPLING SHALL BE USED (NO UNIONS). 3.) ENTIRE SYSTEM MUST HOLD 10#PRESSURE TEST. 1.) EXPOSE ALL NEW PIPING 2.) REMOVE UNION OR INSTALL AGA BLDG SHUT OFF VALVE. 3.) AIR TEST TO 10#. 4.) DO NOT TEST THROUGH APPLIANCES. |