Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/25/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CAN NOT HAVE A FLEX CONNECTOR EXTEND THROUGH HOUSING OF APPLIANCE SEE SECTION: 1212.0 94 UPC 2.) WATER HTR P&T DRAIN REQUIRES A UNION IN LINE SEE SECTION: 609.4 94 UPC 3.) WATER HTR FLU VENT REQUIRES (3) SCREWS PER JOINT AND VENT CONNECTOR SECTION: 514.2 4.) MUST REMOVE EXSISTING ASBESTOS FLUE VENT & REPLACE WITH DBC WALL B-VENT & CAP. 5.) CONNECT ALL SHUT OFF VALVES IN LINE 6.) RE-TEST SYSTEM 7.) VERY POOL INSTALLATION OF BLOCKS FOR GAS LINE ON ROOF SECTION: 310.1 96 UPC 8.) CAN NOT USE ANY USED PIPE ON A NEW GAS SYSTEM. I MUST VERIFY APPR. STAMPS ON GAS LINE (NO MARKINGS ON PIPE) 9.) MUST PAY REINSPECTION FEE BEFORE NEXT INSPECTIONS. |