Permit: T02PL00057

Parcel: 112052790

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T02PL00057

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2002 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
01/14/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) EXSISTING SYSTEM IS STILL NOT HOLDING AIR PRESSURE TEST.
01/11/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) EXSISTING GAS LINE IS NOT HOLDING PRESSURE TEST.
01/10/2002 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) SYSTEM APPEARS TO HAVE A SMALL LEAK. SOAP DOWN ALL EXPOSED GAS LINE FITTINGS AND SHUT OFF VALVES TO MAYBE LOCATE THE LEAK. 2.) PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVE @ RANGE. 3.) RE TEST SYSTEM 10LBS MIN.