Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T02PL00057
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2002 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* | |
| 01/14/2002 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) EXSISTING SYSTEM IS STILL NOT HOLDING AIR PRESSURE TEST. | |
| 01/11/2002 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) EXSISTING GAS LINE IS NOT HOLDING PRESSURE TEST. | |
| 01/10/2002 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) SYSTEM APPEARS TO HAVE A SMALL LEAK. SOAP DOWN ALL EXPOSED GAS LINE FITTINGS AND SHUT OFF VALVES TO MAYBE LOCATE THE LEAK. 2.) PROVIDE AGA OR CSA APPROVED GAS SHUT OFF VALVE @ RANGE. 3.) RE TEST SYSTEM 10LBS MIN. |