Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) EXTENDER RINGS ARE NEEDED WHERE MORE THAN 1/4" FROM BOX TO DEVICE OR BRING BOX FLUSH WITH DRYWALL 2.) WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM. 3.) PROTECT CABLE FOR WATER HEATER AND FILL UNUSED OPENING. 4.) PLEASE VERIFY PERMIT FOR WATER HEATER NEW. 5.) INSTALL ALL LIGHT FIXTURES THAT ARE MISSING AND COVER PLATES. 6.) OUTSIDE BACK LIGHT BROKEN AND NEEDS TO BE WEATHER PROOF. 7.) SERVICE IS IN DIS REPAIR,WE HAVE MULTIPOLE TERMANATIONS AND UNDER SIZED FOR LOADS. 8.) CANNOT FIND OVER CURRENT DEVICE OR FOR WATER HEATER 9.) A LICENSED L-11 ELECTRICAL CONTRACTOR TO PERFORM WORK. |