Permit: T02EL02298

Parcel: 120062190


Addresses:

102 E PALMDALE ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/25/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0210*GROUND ROD MUST BE A MIN OF 6 FT. APART IDENTIFY ALL CIRCUITS.
A SEALING FITTING IS REQUIRED FOR 1/2" CONDUIT ENTRY TOP SIDE OF PANEL.
NEED TO BOND INTERIOR WATER
GAS BOND ON WRONG PLACE. PLEASE BOND GAS ON SIDE OF METER (CUSTOMER SIDE.)