Permit: T02EL01756

Parcel: 110071440


Addresses:

2628 N FAIR OAKS AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/28/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.)NOTES INSTALL BUSHED CONNECTOR AT END OF CONDUIT SLEEVES TO PROTECT CABLE FROM ABRASION 300-15C NEC. 2.) SUPPORT RISER USING MIN. 1/4" BOLTS WITHIN 3' OF ENCLOSURE..