Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 09/13/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 4 NEED TO SEE INSIDE NEW WIRING. 1. ADDRESS LABEL NEEDS TO BE SCREWED OR RIVITED TO SERVICE ENCLOSURE. 2. TOP PENETRATION TO FAR FORWARD ON ENCLOSURE, NOT SEALED PROPERLY, SHOULD HAVE SEALING LOCKNUT, MOVE BACK TO AVOID HAVING TO ALTER DESIGN OF DEAD FRONT, REPAIR OR REPLACE DEAD FRONT, 110-3, 110-12 NEC. 3. INSTALL BOND BUSHING ON 1" PENETRATION ON SIDE. PLUG UNUSED OPENING. |
|
| 08/20/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 08/19/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
| 08/15/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* |