Permit: T02EL01600

Parcel: 113102860


Addresses:

1833 E WATER ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/17/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/13/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 4 NEED TO SEE INSIDE NEW WIRING. 1. ADDRESS LABEL NEEDS TO BE SCREWED OR RIVITED TO SERVICE ENCLOSURE.
2. TOP PENETRATION TO FAR FORWARD ON ENCLOSURE, NOT SEALED PROPERLY, SHOULD HAVE SEALING LOCKNUT, MOVE BACK TO AVOID HAVING TO ALTER DESIGN OF DEAD FRONT, REPAIR OR REPLACE DEAD FRONT, 110-3, 110-12 NEC.
3. INSTALL BOND BUSHING ON 1" PENETRATION ON SIDE. PLUG UNUSED OPENING.
08/20/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
08/19/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
08/15/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*