Permit: T02EL01600

Parcel: 113102860


Addresses:

1833 E WATER ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
08/19/2002 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*
08/15/2002 ELECTRIC - UNDERGROUND Denied IVRS - Inspection 0999*1.) SUPPORT CONDUIT AT SIDE OF PANEL AND TIGHTEN FITTINGS 2.) A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE BUSS. 3.) A PERMANENT ADDRESS LABEL IS NEEDED. 4.) A GAS BOND AND WATER BOND ARE NEEDED. 5.) NEED ACCESS TO INTERIOR TO INSPECT NEW CONNECTIONS.