Permit: T02EL01254

Parcel: 13311002S

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T02EL01254

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
06/19/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0165*CORRECTIONS THE CITY OF TUCSON AMENDED ELECTRICAL CODE REQUIRES.1.) A SMOKE DETECTOR BE INSTALED IN EACH SLEEPING ROOM. LOCATE PER MANUFACTURERS. INSTRUCTIONS. IN ANY CASE NOT TO BE LOCATED CLOSER THAN THREE FEET 3' TO AIR REGISTERS, IF ON WALL NOT LOWER THAN 12" NOR CLOSER THAN 6" TO CIELING. 2. KITCHEN COUNTER RECEPTACLES SHOULD BE GFI. TYPE CORRECT & RECALL INSPECTION.