Permit: T02EL01236

Parcel: 13817029B


Addresses:

7130 S NOGALES HY


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T02EL01236

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2002 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
06/17/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0245*1.) OPEN J-BOX WITH EXPOSED WIRING WEST END OF BLD, CEILING AREAS, SUB PANEL MISSING BREAKER BLANKS IN DEADFRONT. 2.) LOOSE RECEPT BOXES UNDER COUNTER, SHOULD BE FLUSH MTD. NEED RECEPT COVERS. WEST END OF BLD. 3.) CAP OFF OR ABANDON FLEX & WIRING, SEAL KO AT SUBPANEL ON WALL, LOOSE J-BOXES EXPOSED WIRING ABOVE CEILING AT WEST BAND STAND AREA. 4.) SUPPORT CONDUIT RUN ALONG WALL SOUTH END, RE ATTACH WHERE LOOSE FITTINGS, 4.) REMOVE EXTENSION CORDS, REMOVE UNUSED FLEX, WIRING ETC. NOT BEING USED, THRU OUT 6.) CONDUIT WIRING ON ROOF NOT COMPELTE, NOT UP TO CODE. ALL ELECTRICAL WORK TO BE DONE BY L-11 LICENSED CONTR. RE CALL INSP. WHEN DONE.