Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 06/27/2002 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 06/17/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0245*1.) OPEN J-BOX WITH EXPOSED WIRING WEST END OF BLD, CEILING AREAS, SUB PANEL MISSING BREAKER BLANKS IN DEADFRONT. 2.) LOOSE RECEPT BOXES UNDER COUNTER, SHOULD BE FLUSH MTD. NEED RECEPT COVERS. WEST END OF BLD. 3.) CAP OFF OR ABANDON FLEX & WIRING, SEAL KO AT SUBPANEL ON WALL, LOOSE J-BOXES EXPOSED WIRING ABOVE CEILING AT WEST BAND STAND AREA. 4.) SUPPORT CONDUIT RUN ALONG WALL SOUTH END, RE ATTACH WHERE LOOSE FITTINGS, 4.) REMOVE EXTENSION CORDS, REMOVE UNUSED FLEX, WIRING ETC. NOT BEING USED, THRU OUT 6.) CONDUIT WIRING ON ROOF NOT COMPELTE, NOT UP TO CODE. ALL ELECTRICAL WORK TO BE DONE BY L-11 LICENSED CONTR. RE CALL INSP. WHEN DONE. |