Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/14/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES OWNER OF DWELLING NOT HOME 1.) CHASE NIPPLE NOT AN APPROVED WIRING METHOD FOR CONNECTION OF 1" LB. MUST MUST USE CLOSE NIPPLE LOCKNUT EACH END AND GROUNDING BUSHING BECAUSE OF CONCENTRIC KO. 2.) MUST BOND GAS PIPING. 3.) NEW WIRING INSIDE SUB-PANEL NOT PER CODE, SUB PANEL MUST BE ACCESSABLE ALSO COMPLETE WIRING. |
| 03/21/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210* |