Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/26/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0215* CONDUIT CONNECTIONS AND WIRING, OTHER THAN THE UTILITY COMPANY CONDUCTORS, ARE NOT PERMITTED I THE SECTION RESERVED FOR THE UTILITY COMPANY TEP. SEE TEP SERVICE MANUAL AND NEC ART 230. REMOVAL OF THE METER SHOULD NOT BE REQUIRED TO SERVICE ANY CUSTOMER WIRING. THANKS |
| 02/28/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*1.) A SEALING FITTING IS NEEDED ON ALL FITTINGS INSTALLED ABOVE THE BUSS. 2.) PLEASE MAKE CONNECTIONS FOR SEALITITE CORRECTLY AND TIGHTEN ALL FITTINGS. |