Permit: T02EL00401

Parcel: 115010280


Addresses:

2320 N 2ND AV

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/26/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215* CONDUIT CONNECTIONS AND WIRING, OTHER THAN THE UTILITY COMPANY CONDUCTORS, ARE NOT PERMITTED I THE SECTION RESERVED FOR THE UTILITY COMPANY TEP. SEE TEP SERVICE MANUAL AND NEC ART 230. REMOVAL OF THE METER SHOULD NOT BE REQUIRED TO SERVICE ANY CUSTOMER WIRING. THANKS
02/28/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*1.) A SEALING FITTING IS NEEDED ON ALL FITTINGS INSTALLED ABOVE THE BUSS. 2.) PLEASE MAKE CONNECTIONS FOR SEALITITE CORRECTLY AND TIGHTEN ALL FITTINGS.