Permit: T02CM05846

Parcel: 133233290


Addresses:

7671 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T02CM05846

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2003 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection 0000*
07/25/2003 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection 0000*
07/23/2003 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection 0000*/ 1) PLEASE PROVIDE INFORMATION FOR PRIMARY FEEDER CONDUCER SIZES FROM ENGINEER. NOT ON PLANS. 2) A DISCONNECTING MEANS IS NEEDED TO PROTECT SECONDARY CONDUCER PER TAP RULE 240.21. 3) CHECK A/C TAPS.