Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 02/26/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 11/06/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MUST COMPLETE FRAMING, PLUMBING, GAS, MECHANICAL 2) RECALL PRIOR TO INSULATING OR SHEET ROCKING FOR INSPECTION |
| 10/09/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) 1/2 PLAN CALLS FOR OUTLET OUTSIDE REAR, GROUND ALL METAL ELECTRIC BOXES 2) INSTALL METAL BANG PLATES ALL PENETRATIONS THROUGH WOOD 3) REMOVE ALL OLD UNUSED OUTLETS, BOXES, 4) PLAN CALLS FOR 3 GANG BOX AT FRONT DOOR AND LITHT UNDER FRONT PORCH AND ONLY ONE LIGHT IN CARPORT 5) WHAT IS DOUBLE GANG BOX ON LIVING ROOM WALL FOR ? ( ACCROSS FROM PLAN SWITCH FOR COOLER) 6) INSTALL NAIL PROTECTION OVER ALL WIRES THAT MIGHT BE NAILED INTO 7) MUST USE APPROVED BOXES FOR CEILING FANS 8) BEDROOM SWITCHES NOT PER PLAN 9) SMOKE DETECTORS TO BE MINIMUM 36" AWAY FROM MECHANICAL GRILL 10) USE ROMEX CONNECTORS INTO ALL METAL BOXES OR BUSHING 11) BATH ELECTRIC NOT TO PLAN 12) KITCHEN ELECTRIC NOT PER PLAN 13) STOPPED INSPECTION; SUBMIT ASBUILT DRAWINGS FOR APPROVAL OR REWIRE TO PLAN |