Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T02CM05776

Parcel: 130054940


Addresses:

2266 S FORGEUS AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/01/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/26/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
11/06/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) MUST COMPLETE FRAMING, PLUMBING, GAS, MECHANICAL 2) RECALL PRIOR TO INSULATING OR SHEET ROCKING FOR INSPECTION
10/09/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) 1/2 PLAN CALLS FOR OUTLET OUTSIDE REAR, GROUND ALL METAL ELECTRIC BOXES 2) INSTALL METAL BANG PLATES ALL PENETRATIONS THROUGH WOOD 3) REMOVE ALL OLD UNUSED OUTLETS, BOXES, 4) PLAN CALLS FOR 3 GANG BOX AT FRONT DOOR AND LITHT UNDER FRONT PORCH AND ONLY ONE LIGHT IN CARPORT 5) WHAT IS DOUBLE GANG BOX ON LIVING ROOM WALL FOR ? ( ACCROSS FROM PLAN SWITCH FOR COOLER) 6) INSTALL NAIL PROTECTION OVER ALL WIRES THAT MIGHT BE NAILED INTO 7) MUST USE APPROVED BOXES FOR CEILING FANS 8) BEDROOM SWITCHES NOT PER PLAN 9) SMOKE DETECTORS TO BE MINIMUM 36" AWAY FROM MECHANICAL GRILL 10) USE ROMEX CONNECTORS INTO ALL METAL BOXES OR BUSHING 11) BATH ELECTRIC NOT TO PLAN 12) KITCHEN ELECTRIC NOT PER PLAN 13) STOPPED INSPECTION; SUBMIT ASBUILT DRAWINGS FOR APPROVAL OR REWIRE TO PLAN