Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/02/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS FROM 12/24/03 MADE OK. 2) GENERAL CONTRACTOR TO ENFORCE MINIMUM INSTALLATION STANDARD AND WORKMANSHIP MANNER OF INSTALLATION. 3) OK FOR C OF O PENDING ANY OTHER INSP. |
| 12/24/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MUST STRAP DOWN EXPANSION TANK. 2) MUST CUALK ALL FIXTURES. 3) ONLY ONE SLIP JOINT ALLOWED ON TRAP ARM FOR SINK IN ADMIN BLDG. 4) NO C.O. FOR HAND SINK IN KITCHEN. 5) TRIPLE COMPT SINK REQUIRES A TRAP. 6) ART RM SINK TRAP ARM EXCEEDS 135o. 7) ART RM SINK REQUIRES C.O. 8) T&P DRAIN RQUIRES 90o. |