Permit: T02CM05567

Parcel: 137070570


Addresses:

5093 S LIBERTY AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
01/02/2004 PLUMBING - ROUGH, SOIL Approved
11/07/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) GREASE TRAP INSTALLED PER PLAN AS NOTED ON PLIL. 2) OK TO BACKFILL.
07/01/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) 60 POUNDS AIR PRESSURE TEST IS OK 2) THIS INSPECTION IS FOR YARD WATER SERVICE FOR BLDG #A, B, C, D AND E 3) NOTE: SEE DETAIL 213 ON P-1.2 ? BLOCKS
06/30/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION
06/27/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK 2) THIS INSPECTION IS FOR UG PLBG IN ROOMS 140, 141, 136, 137 AND NOTED ON PLAN 3) OK FOR BACKFILL
06/23/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK 2) THIS INSPECTION IS FOR ROOM #112, 108, 109 AND 105 AND BLDG SEWER AS NOTED ON PLAN 3) OK TO BACKFILL TRENCH
06/20/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*
06/19/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000* HAD MEETING WITH PLBG CONTRANCTOR ON PLAN ISSUES.
06/18/2003 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT READY FOR INSPECTION
06/17/2003 PLUMBING - ROUGH, SOIL Denied 1) 4 X 3 REDUCER FOR SOUTH BLDG. SEWER 2) NO TWO WAY CLEANOUT EACH BLDG. SEWER REQUIRES A TWO WAY CLEANOUT
06/13/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) CANNOT HAVE FLAT FACED BUSHING IN HORIZONTAL DRAINAGE SEE SEC. 311.5 94 UPC INTERPERTATION
06/13/2003 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK 2) BLDG DRAIN IS STUBBED OUT OF BLDG ONLY 3) THIS INSPECTION IS BLDG C ONLY 4) OK FOR BACKFILL