Permit: T02CM05314

Parcel: 13316013B


Addresses:

6500 E GRANT RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/30/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE 2) OK FOR C OF O
07/23/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) PERMANENTLY IDENTIFY EQUIPMENT ON ROOF 2) PROVIDE WEATHER CAP FOR FLUE VENT ON A/C UNITS 3) CONNECT CONDENSATE DRAIN LINE ALL UNITS 4) PROVIDE AN OUTSIE AIR INTAKE ALL NEW UNITS 5) CONDENSORS ON ROOF MUST BE ON AN APPROVED BASE. 6) A/C-25 OVERFUSED 7) FINISH INSTALLING EXHAUST FAN 8) USE SUN RESISTANT CONTROL WIRING ON CONDENSORS OR USE CONDUIT 7) A/C-24 LABEL DATA PLATE WITH PROPER HEAT KITCHEN INSTALLED AND FUSE ACCORDINGLY