Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/30/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE 2) OK FOR C OF O |
| 07/23/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PERMANENTLY IDENTIFY EQUIPMENT ON ROOF 2) PROVIDE WEATHER CAP FOR FLUE VENT ON A/C UNITS 3) CONNECT CONDENSATE DRAIN LINE ALL UNITS 4) PROVIDE AN OUTSIE AIR INTAKE ALL NEW UNITS 5) CONDENSORS ON ROOF MUST BE ON AN APPROVED BASE. 6) A/C-25 OVERFUSED 7) FINISH INSTALLING EXHAUST FAN 8) USE SUN RESISTANT CONTROL WIRING ON CONDENSORS OR USE CONDUIT 7) A/C-24 LABEL DATA PLATE WITH PROPER HEAT KITCHEN INSTALLED AND FUSE ACCORDINGLY |