Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2003 | PLUMBING - INTERMEDIATE | Approved | ||
| 06/26/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) PROVIDE APPROVAL TO COVER WALLS IN FOOD SERVICE AREA. 2) THE POINT OF VENT MAY NOT BE BELOW THE ?? OF THE TRAP 3) ALL THREE COMPARMENTS OF 2 COMP SINK ARE DIRECTLY WASTED . IS A VEGETABLE PREP SINK ALSO REQUIRED? | |
| 06/19/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* NORTHEAST CORNER OF BUILDING . WATER TEST OK. OK TO COVER WALL | |
| 06/13/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/UNDERGROUND ONLY FOR PHARMACY TEST OK, SUBJECT TO APPROVED REVISED PLAN REDLINING ON JOB | |
| 05/23/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 05/20/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*FOOD COURT AREA NOT READY. PLEASE PROVIDE WATER TEST AS REQUIRED. PLEASE PROVIDE CLEVIS HANGERS AS NEEDED. | |
| 05/19/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
| 05/08/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1.) MEN'S #115 AND WOMENS #116 CARRIERS AND WATER STUBS RELOCATED OK URINAL WASTE AND VENT W/CLEAN OUTS OK 2.) FOOD SERVICE #123 DEMO'D PIPING. BELOW FLOOR CAPPED OFF OK TO COVER. 3.) TRAP PRIMERS WILL REQUIRE ISOLATION VALVE AND UNION. |