Permit: T02CM05314

Parcel: 13316013B


Addresses:

6500 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/31/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
12/06/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
10/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
12/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH PREVIOUS INSPECTION ITEM FOR LISTING
07/30/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) VERIFY LISTING LABELS FOR EXHAUST FANS ABOVE GARDEN CENTER. OK SIGN ELECTRIC. OK ROOF (UPPER)
07/29/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) VERIFY LISTING LABEL ON EXHAUST FANS ABOVE GARDEN CENTER 2) WE HAVE LOOSE FITTINGS AND NO GROUND IN METAL BOX GARDEN AREA TV, ALSO INSTALL STRAPS CORRECTLY 3) WILL CHECK ROOF NEXT INSPECTION
07/24/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
07/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) POWER OUTLETS AND JUNCTION BOXES FOR 14 CHECKSTANDS ACCESSABLE PROBLEMS. M/C CABLES STRAPPED TO ACCESS CENTER. 2) USE APPROVED FITTINGS OR NIPPLES BETWEEN BOXES. 3) WE HAVE OPEN JUNCTION BOXES WITH EXPOSED CONDUCTORS AND MISSING SEALS AND PARTIAL FITTINGS ABOVE CHECKSTANDS. 4) OPEN JUNCTION BOXES AT CHECK STANDS. 5) OUTLETS IN METAL BOXES NOT GROUNDED.
07/11/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/OK TEMP C/O FOOD AVENUE. CALL FOR MONDAY TO CHECK ITEM AND PREVIOUS INSP.
07/10/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
07/07/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
07/02/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) OK KITCHEN EQUIPMENT FOR LABELING, OK PLUG MOLD. PHARMACY: FINISH WIRING UNDER COUTNER 2) NEED CORRECT PANEL COVER AND LABELS ON OUTSIDE OF COVER. FOOD AVENUE: 1) APPROVED EXTENDER RINGS WHERE 1/4" OR MORE FROM BOX TO SURFACE ARE NEEDED-METAL NOT APPROVED 370.20 2) TERMINATE M/C CONNECTOR AT MENU BOARD SIGNS 3) FINISH LIGHT HARD CEILING 4) CORD TO BE INTO STRAIN CONNECTORS 5) FILL UNUSED OPENINGS IN BOXES AND INSTALL COVERS-ABOVE HARD CEILING 6) SUPPORT M/C CABLE-ABOVE HARD CEILING 7) PANEL HOME RUNS AND PANEL SCHEDULES DO NOT MATCH. PLEASE REVISE PLANS AS TO WHAT IS CORRECT 8) WHERE IS WATER HEATER DISCONNECT ?
06/25/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
06/24/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*