Permit: T02CM05314

Parcel: 13316013B


Addresses:

6500 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/29/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
07/25/2003 ELECTRIC - ABOVE CEILING Partial Approval 1) SUPPORT M/C CABLE 2) TIGHTEN LOOSE FITTINGS 3) GROUND JUNCTION BOXES AT POWER POLES 4) FILL UNUSED OPENINGS ROOF: 1) DISCONNECT DOOR TO OPEN 90 DEGREE 2) BOND ENCLOSURES FREEZER CONDENSORS AND TIGHTEN CONDUIT FITTINGS 7) DOUBLE TAP A/C + 2 8) OK-L-11 DISCONNECT AND PANEL, OK-T-11 TRANSFORMER
07/24/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/CASH CHECKOUT STANDS HAVE NEC CODE VIOLATIONS. STANDS ARE LISTED BY UL. THESE CORRECTIONS SHOULD BE TAKEN CARE OF FOR CODE COMPLIANCE. 1) JUNTION BOXES NOT GROUNDED, 250-148. 2) USE APPROVED FITTINGS OR NIPPLES FOR BOX CONNECTIONS 110-3.

OK, PANEL LP-11.

1) A BUSHING IS NEEDED TO PROTECT CONDUCTOR IN DISSCONNECT AND JUNCTION BOX. 2) CLEAN SURFACE UNDER GROUND LUG 250-12. 3) FINISH LABELING EQUIPMENT, 110-22. 4) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING, 250-8.
07/23/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*
06/30/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) OK ABOVE CEILING IN PHARMACY
06/27/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED BY CONTRACTOR
06/26/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*/ PHARMACY: 1) SUPPORT WIRES TO BE IN OPPISITE DIRECTIONS 2) SUPPORT M/C CABLE AS PER CODE-12" WITHIN OF BOX AND CONDUCT-3' FROM BOX 3) INSTALL ALL BOX COVERS 4) FILL UNUSED OPENINGS IN BOXES 5) CORD CAN NOT BE ABOVE CEILIJNG 400.7 AND 400.8 6) TIGHTEN LOOSE FITTINGS 7) M/C CABLE TO TERMINATE TO CONDUIT 8) PROBABLY INSTALL FLEX CONNECTORS 9) A REFEE MAY BE ACCESSED IF WE HAVE CONTINUED REPEAT CORRECTIONS
06/25/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
06/24/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*
06/20/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
06/16/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) RELOCATE END CAPS ARE NEEDED 2) SUPPORT WIRE TO BE IN OPPOSITE DIRECTIONS 3) SUPPORT JUNCTION BOXES