Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 07/25/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | 1) SUPPORT M/C CABLE 2) TIGHTEN LOOSE FITTINGS 3) GROUND JUNCTION BOXES AT POWER POLES 4) FILL UNUSED OPENINGS ROOF: 1) DISCONNECT DOOR TO OPEN 90 DEGREE 2) BOND ENCLOSURES FREEZER CONDENSORS AND TIGHTEN CONDUIT FITTINGS 7) DOUBLE TAP A/C + 2 8) OK-L-11 DISCONNECT AND PANEL, OK-T-11 TRANSFORMER | |
| 07/24/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/CASH CHECKOUT STANDS HAVE NEC CODE VIOLATIONS. STANDS ARE LISTED BY UL. THESE CORRECTIONS SHOULD BE TAKEN CARE OF FOR CODE COMPLIANCE. 1) JUNTION BOXES NOT GROUNDED, 250-148. 2) USE APPROVED FITTINGS OR NIPPLES FOR BOX CONNECTIONS 110-3. OK, PANEL LP-11. 1) A BUSHING IS NEEDED TO PROTECT CONDUCTOR IN DISSCONNECT AND JUNCTION BOX. 2) CLEAN SURFACE UNDER GROUND LUG 250-12. 3) FINISH LABELING EQUIPMENT, 110-22. 4) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING, 250-8. |
|
| 07/23/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* | |
| 06/30/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) OK ABOVE CEILING IN PHARMACY | |
| 06/27/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CANCELLED BY CONTRACTOR | |
| 06/26/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*/ PHARMACY: 1) SUPPORT WIRES TO BE IN OPPISITE DIRECTIONS 2) SUPPORT M/C CABLE AS PER CODE-12" WITHIN OF BOX AND CONDUCT-3' FROM BOX 3) INSTALL ALL BOX COVERS 4) FILL UNUSED OPENINGS IN BOXES 5) CORD CAN NOT BE ABOVE CEILIJNG 400.7 AND 400.8 6) TIGHTEN LOOSE FITTINGS 7) M/C CABLE TO TERMINATE TO CONDUIT 8) PROBABLY INSTALL FLEX CONNECTORS 9) A REFEE MAY BE ACCESSED IF WE HAVE CONTINUED REPEAT CORRECTIONS | |
| 06/25/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
| 06/24/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* | |
| 06/20/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
| 06/16/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) RELOCATE END CAPS ARE NEEDED 2) SUPPORT WIRE TO BE IN OPPOSITE DIRECTIONS 3) SUPPORT JUNCTION BOXES |