Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 07/11/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 06/24/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) AREA FOR FITTING ROOMS OCCUPIED WITHOUT TEMP C OF O FINALS AND ELECTRIC. ( FITTING ROOMS: 1) PROTECT CONDUCTORS ENTERING FIXTURE 2) AN APPROVED EXTENDER RING IS NEEDED FOR BOXES MORE THAN 1/4" FROM BOX TO SURFACE 3) LIGHT FIXTURE SUPPORT WIRES TO BE IN OPPISITE DIRECTIONS (ELECTRONICS: 1) JUNCTION BOX TO BE ACESSIBLE 2) VDV CABLE PASSING THROUGH ACCESS COVER 3) SUPPORT M/C CABLE WITHIN 12" OF BOXES 4) BOXES TO BE GROUNDED | |
| 06/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK BATHROOM PHARMACY 2) OK ABOVE CEILING IN FOOD AVENUE 3) OK EAST WALL ELECTRONICS | |
| 06/17/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
| 06/11/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK UNDERGROUND CONDUITS AND 6 FLOOR BOXES AT ELECTRONICS | |
| 06/05/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) SUPPORT CONDUIT WITHIN 3' OF BOXES 2) NO MORE THAN 360 DEGREE IN A CONDUIT RUN 3) WHAT ARE UNFINISHED CONDUITS AND M/C CABLE FOR ? | |
| 06/04/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) UNCOVER WALLS FOR INSPECTION PHARMACY 2) CANNOT STACK LUGS IN T-11 3) SIZE BONDING JUMPER PER 250-66 AND GROUNDING ELECTRODE 4) LABEL PANEL CIRCUIT DIRECTORYS 5) VERIFY FRS FUSES FOR T-11 FEED 6) VERIFY LOADS AND PLANS FOR "LUE-2" 7) NEED APPROVED PLANS ON SITE IF NOT REFLECTIVE OF WORK DONE. PLEASE REVISE AND HAVE STAMPED CITY APPROVED | |
| 05/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK FLOOR BOXES & PVC CONDUIT UNDER FLOOR AT JEWELRY DEPT. TO POLE. | |
| 05/18/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK WALLS AT FITTING ROOMS 1) HOLD DOWN STRAPS TO BE EFFECTIVE 2) FILL UNUSED OPENG IN BOX | |
| 05/14/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*SUPPORT M/C CABLE AS PER CODE 2.) OPEN NEW WALLS FOR INSPECTION 3.) PLEASE ADD 02010 ELECTRIC UNDERGROUND TO PERMIT. OK 2 FLOOR BOXES & CONDUIT OK WALLS FOOD COURT. |