Permit: T02CM05314

Parcel: 13316013B


Addresses:

6500 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/29/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
07/11/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
06/24/2003 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) AREA FOR FITTING ROOMS OCCUPIED WITHOUT TEMP C OF O FINALS AND ELECTRIC. ( FITTING ROOMS: 1) PROTECT CONDUCTORS ENTERING FIXTURE 2) AN APPROVED EXTENDER RING IS NEEDED FOR BOXES MORE THAN 1/4" FROM BOX TO SURFACE 3) LIGHT FIXTURE SUPPORT WIRES TO BE IN OPPISITE DIRECTIONS (ELECTRONICS: 1) JUNCTION BOX TO BE ACESSIBLE 2) VDV CABLE PASSING THROUGH ACCESS COVER 3) SUPPORT M/C CABLE WITHIN 12" OF BOXES 4) BOXES TO BE GROUNDED
06/20/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK BATHROOM PHARMACY 2) OK ABOVE CEILING IN FOOD AVENUE 3) OK EAST WALL ELECTRONICS
06/17/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
06/11/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK UNDERGROUND CONDUITS AND 6 FLOOR BOXES AT ELECTRONICS
06/05/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) SUPPORT CONDUIT WITHIN 3' OF BOXES 2) NO MORE THAN 360 DEGREE IN A CONDUIT RUN 3) WHAT ARE UNFINISHED CONDUITS AND M/C CABLE FOR ?
06/04/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) UNCOVER WALLS FOR INSPECTION PHARMACY 2) CANNOT STACK LUGS IN T-11 3) SIZE BONDING JUMPER PER 250-66 AND GROUNDING ELECTRODE 4) LABEL PANEL CIRCUIT DIRECTORYS 5) VERIFY FRS FUSES FOR T-11 FEED 6) VERIFY LOADS AND PLANS FOR "LUE-2" 7) NEED APPROVED PLANS ON SITE IF NOT REFLECTIVE OF WORK DONE. PLEASE REVISE AND HAVE STAMPED CITY APPROVED
05/20/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK FLOOR BOXES & PVC CONDUIT UNDER FLOOR AT JEWELRY DEPT. TO POLE.
05/18/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK WALLS AT FITTING ROOMS 1) HOLD DOWN STRAPS TO BE EFFECTIVE 2) FILL UNUSED OPENG IN BOX
05/14/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*SUPPORT M/C CABLE AS PER CODE
2.) OPEN NEW WALLS FOR INSPECTION
3.) PLEASE ADD 02010 ELECTRIC UNDERGROUND TO PERMIT.
OK 2 FLOOR BOXES & CONDUIT
OK WALLS FOOD COURT.