Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/13/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ LETTERS ON TORQUE AND J-BOX OK TO GO TO FILES. ALL ITEMS OF LAST INSP PER DAN S.C. CORRECTED. ALSO AC UNITS ON ROOF OK WITH LABELS AND BUSHINGS PER MECH INSP. |
| 04/08/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ NOTES: 1) NEED LETTERS FROM ARCH. AS REQUESTED LAST INSP. 3/30/04. 2) COMPLETE ITEMS 2, 4, 6 AND 3, INSP. 3/25/04 |
| 03/30/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) UFER FOR NEW BLD NOT INSPECTED, INSTALL ALTERNATE GROUNDING SYSTEM APPROVED BY ARCH. 2) NEED LETTER OF TORQUE FOR NEW SWICH GEAR. 3) BOND WTR AND GAS PIPING AT NEW BLD. 4) BOND NIPPLES AT CT CAN AND NEW SWITCH GEAR. 5) MAIN BONDING JUMPER NOT CONNECTED. 6) LABEL BREAKERS IN NEW SWITCH GEAR. 7) SECURE GROUNDING ELECTRODE CONDUCTOR AT SWITXH GEAR TERMINATION. 8) NEED LETTER FROM ARCH FOR APPROVAL OF USE OF EXIST CT CAN AT TERMINATION BOX. |
| 03/25/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) SCREWS MISSING ON PANEL COVER. 2) INSULATING BUSHING REQUIRED ON 2" FEEDER CONDUIT TERMINATION AT PANEL MP. 3) LABEL DISCONNECTS ON ROOF INSTALL BUSHINGS IN AC DISCONNECTS ON ROOF FOR LOAD CONDUCTORS. 4) CITY OF TUCSON INSPECTOR DID NOT INSPECT INSTALLATION OF GROUNDING OR SERVICE SWITCHGEAR INSTALLATIONS (1600 AMP). NEW SERVICE IS ENERGIZED WITHOUT CITY AUTHORIZATION . CALL R MAJUTA ASAP 909-5184 CELL OR . STEVE LONG 791-5550 EXT 147. |